Hukseflux Pyranometers
Purpose
The purpose of this plugin is to collect data from Hukseflux pyranometers via Modbus.
Usage
This plugin collects from the Hukseflux pyranometer sensors. It uses the Modbus TCP Specification, and collects from Serial or IP connected sensors. The following models are supported:
SR30-M2-D1This plugin relies on the Modbus Ardexa plugin. The following data points are collected:
Variable Name Units
======================================================
Device Address
Com Settings
Solar Radiation Temp Comp W/m^2
Solar Radiation W/m^2
Temperature ºC
Resistance Ohm
Scaling Factor Irradiance
Scaling Factor Temperature
Voltage mV
Model 1 High
Model 1 Low
Model 2 High
Model 2 Low
Model 1
Model 2
Serial Number
Sensitivity mV/(W/m^2)
Response Time Calibration s
Resistance Calibration s
Calibration Date YYYYMMDD
Firmware Version
Hardware Version
Sensitivity History 1 mV/(W/m^2)
Calibration Date History 1 YYYYMMDD
Sensitivity History 2 mV/(W/m^2)
Calibration Date History 2 YYYYMMDD
Sensitivity History 3 mV/(W/m^2)
Calibration Date History 3 YYYYMMDD
Sensitivity History 4 mV/(W/m^2)
Calibration Date History 4 YYYYMMDD
Sensitivity History 5 mV/(W/m^2)
Calibration Date History 5 YYYYMMDD
Polynomial Temperature Coefficient a
Polynomial Temperature Coefficient b
Polynomial Temperature Coefficient c
Relative Humidity %
Internal Pressure mbar
Tilt º
Fan Speed rpm
Heater Current A
Fan Current A Arguments
Arguments are as follows:
endpoint. This is either a serial device like/dev/ttyS0or an IP or DNS like192.168.1.15bus_addresses. A Modbus address in the range 2-255. This can be a hyphenated list like3-10or a list like2,5,7,9--port. This is an optional parameter used in an Ethernet gateway, and is the TCP port used for the gateway. Default is502--attempts. This is an optional parameter, and determines how many times to times to attempt to read an inverter value. Default is1--delay. This is the delay in seconds between inverter send and receive commands, AND ifattempts> 1. Fractions like0.3can be used. Default is0.05--stop_on_any_command_fail. If this is specified, then any Modbus commands that fail will stop all further queries for all bus addresses and attempts.--serial_lock. If this is set, the program can only be run one at a time (so as not to overload a Modbus device). If the device being queried is a serial device, this will automatically be set to "on". For IP addresses it is optional.--sampling_rate. If this is defined, and the sampling rate is greater than 1, then all values listed above will be collected as an average. In other words; it will take a sample at the nominated frequency. After X samples defined bysampling_rate, a record will be written and sent to the cloud.
Last updated
Was this helpful?