HEC Freesun Inverters

Purpose

The purpose of this plugin is to collect data from HEC Freesun Inverters via Modbus.

Usage

This plugin reads the data from HEC Freesun Inverters via Modbus. This plugin relies on the Modbus Ardexa plugin. It uses the Modbus TCP Specification, and collects from RS485 or TCP connected inverters. Inverter data will be collected to the solar table. The plugin will be run every 5 minutes, by default. The following data is collected from the inverters. PLEASE NOTE: Energy in the Freesun HEC Inverter says its in MWh, but it actually is in kWh. The status, fault and warning messages have been clarified by Ardexa. See the addendum file called reading_status.png (contact Ardexa for this file).

Variable Name           Units
=============================
AC Voltage 1            V
AC Voltage 2            V
AC Voltage 3            V
Grid Freq               Hz
AC Current 1            A
AC Current 2            A
AC Current 3            A
AC Power                W
Cos Phi
DC Voltage              V
DC Current              A
DC Power                W
Temperature             °C
CCT Temperature         °C
PT100 Temperature       °C
Daily Energy            Wh
Total Energy            Wh
Status
Fault
Warn
Total Hours             h

Arguments

Arguments are as follows:

  • endpoint. This is either a serial device like /dev/ttyS0 or an IP or DNS like 192.168.1.15

  • bus_addresses. An RS485 address in the range 2-63. This can be a hyphenated list like 3-10 or a list like 2,5,7,9

  • --port. This is an optional parameter used in an Ethernet gateway, and is the TCP port used for the gateway. Default is 502

  • --attempts. This is an optional parameter, and determines how many times to times to attempt to read an inverter value. Default is 1

  • --delay. This is the delay in seconds between inverter send and receive commands, AND if attempts > 1. Fractions like 0.3 can be used. Default is 0.05

Last updated