Eaton Inverters
Purpose
The purpose of this plugin is to collect data from Eaton PowerXpert Solar Inverters.
Usage
The purpose of this plugin is to collect data from Eaton PowerXpert Solar Inverters via Modbus. The eaton_powerxpert_1500-2200.txt
(default) file collects data from Eaton PowerXpert Solar Inverters rated to 1500/1670/2000/2200
kW. The plugin uses the Modbus TCP Specification, and collects from TCP connected inverters only. Inverter data will be collected to the solar
table, and will be run every 5 minutes, by default. This plugin relies on the Modbus Ardexa
plugin. The following inverter data will be collected to the solar
table:
Variable Units
=====================================
Status
Display State
Status 2
Active Config Monitor
Sync Status Word
Status Raw
Display State Raw
Status 2 Raw
Active Config Monitor Raw
Sync Status Word Raw
PF Setpoint
AC Power Setpoint W
Reactive Power Setpoint var
DC Current A
DC Voltage V
DC Power W
AC Voltage V
AC Voltage 12 V
AC Voltage 23 V
AC Voltage 31 V
AC Current A
AC Current 1 A
AC Current 2 A
AC Current 3 A
Cos Phi
Reactive Power var
AC Power W
Apparent Power VA
Grid Freq Hz
DC Total Energy Wh
Total Energy Wh
PIB Board Temperature °C
IGBT Module M1A Temp °C
IGBT Module M1B Temp °C
IGBT Module M1C Temp °C
IGBT Module M2A Temp °C
IGBT Module M2B Temp °C
IGBT Module M2C Temp °C
IGBT Module M3A Temp °C
IGBT Module M3B Temp °C
IGBT Module M3C Temp °C
Inlet Water Temp °C
Outlet Water Temp °C
DC Voltage 1 V
DC Voltage 2 V
DC Voltage 3 V
DC Current 1 A
DC Current 2 A
DC Current 3 A
Inlet Water Pressure psi
Outlet Water Pressure psi
Return Flow gpm
IGBT Max Temp °C
Bypass Control 1
Critical Fault 1
Critical Fault 2
Fault 1
Fault 2
Fault 3
Fault 4
Fault 5
Warning 1
Warning 2
Warning 3
Warning 4
Notify Word 1
Inhibit Status
Inputs 1
Inputs 2
Inputs 3
Inputs 4
Inputs 5
Inputs 6
Outputs 1
Outputs 2
Outputs 3
Communication Status
CAN Comm Status
Custom Alert Status
Bypass Control 1 Raw
Critical Fault 1 Raw
Critical Fault 2 Raw
Fault 1 Raw
Fault 2 Raw
Fault 3 Raw
Fault 4 Raw
Fault 5 Raw
Warning 1 Raw
Warning 2 Raw
Warning 3 Raw
Warning 4 Raw
Notify Word 1 Raw
Inhibit Status Raw
Inputs 1 Raw
Inputs 2 Raw
Inputs 3 Raw
Inputs 4 Raw
Inputs 5 Raw
Inputs 6 Raw
Outputs 1 Raw
Outputs 2 Raw
Outputs 3 Raw
Communication Status Raw
CAN Comm Status Raw
Custom Alert Status Raw
```
Arguments
Arguments are as follows:
endpoint
. This is either an IP address like192.168.1.15
bus_addresses
. The bus address of the inverter(s)--port
. This is an optional parameter used in an Ethernet gateway, and is the TCP port used for the gateway. Default is502
--attempts
. This is an optional parameter, and determines how many times to times to attempt to read an inverter value. Default is1
--delay
. This is the delay in seconds between inverter send and receive commands, AND ifattempts
> 1. Fractions like0.3
can be used. Default is0.05
Last updated
Was this helpful?