Janitza Meters
Purpose
The purpose of this plugin is to collect data from Janitza Meters.
Usage
This plugin reads the data from Janitza 604 Pro Meters via serial or TCP. Meter data will be collected to the meter table. By default, it will collect data every 5 minutes, but can collect at a minimum rate of about 0.3 seconds via TCP. The plugin will make 1 attempt (by default) to read the meter. This plugin relies on the Modbus Ardexa plugin. There are 2 configuration files associated with this plugin, namely janitza_604_pro.txt and janitza_604_pro_inverted.txt. The janitza_604_pro_inverted.txt file will invert the values (ie; multiply them by -1), for the 4 x AC Power, 4 x Reactive Power, 3 x Power Factor and 4 x Real Energy values listed below. This makes it easier in some installations to define the imported vs exported power values. The following data will be collected:
Variable Units
=============================
AC Voltage L1 V
AC Voltage L2 V
AC Voltage L3 V
AC Voltage L1-L2 V
AC Voltage L2-L3 V
AC Voltage L3-L1 V
Apparent Current L1 A
Apparent Current L2 A
Apparent Current L3 A
Apparent Current A
AC Power L1 W
AC Power L2 W
AC Power L3 W
AC Power W
Apparent Power L1 VA
Apparent Power L2 VA
Apparent Power L3 VA
Apparent Power VA
Reactive Power L1 var
Reactive Power L2 var
Reactive Power L3 var
Reactive Power var
Power Factor 1
Power Factor 2
Power Factor 3
Grid Freq Hz
Real Energy L1 Wh
Real Energy L2 Wh
Real Energy L3 Wh
Real Energy Wh
Consumed Energy L1 Wh
Consumed Energy L2 Wh
Consumed Energy L3 Wh
Consumed Energy Wh
Delivered Energy L1 Wh
Delivered Energy L2 Wh
Delivered Energy L3 Wh
Delivered Energy Wh
Apparent Energy L1 VAh
Apparent Energy L2 VAh
Apparent Energy L3 VAh
Apparent Energy VAh
Reactive Energy L1 varh
Reactive Energy L2 varh
Reactive Energy L3 varh
Reactive Energy varh
React induct Energy L1 varh
React induct Energy L2 varh
React induct Energy L3 varh
React induct Energy varh
React capac Energy L1 varh
React capac Energy L2 varh
React capac Energy L3 varh
React capac Energy varh
THD U L1 %
THD U L2 %
THD U L3 %
THD I L1 %
THD I L2 %
THD I L3 %Arguments
Arguments are as follows:
endpoint. This is either a serial device like/dev/ttyS0or an IP or DNS like192.168.1.15config_path. This defines the configuration file to use, namelyjanitza_604_pro.txtandjanitza_604_pro_inverted.txt. SeeUsageabove for a discussion on these 2 parameters.bus_addresses. A Modbus address in the range 2-255. This can be a hyphenated list like3-10or a list like2,5,7,9--port. This is an optional parameter used in an Ethernet gateway, and is the TCP port used for the gateway. Default is502--attempts. This is an optional parameter, and determines how many times to times to attempt to read an inverter value. Default is1--delay. This is the delay in seconds between inverter send and receive commands, AND ifattempts> 1. Fractions like0.3can be used. Default is0.05--stop_on_any_command_fail. If this is specified, then any Modbus commands that fail will stop all further queries for all bus addresses and attempts.--serial_lock. If this is set, the program can only be run one at a time (so as not to overload a Modbus device). If the device being queried is a serial device, this will automatically be set to "on". For IP addresses it is optional.--sampling_rate. If this is defined, and the sampling rate is greater than 1, then all values listed above will be collected as an average. In other words; it will take a sample at the nominated frequency. After X samples defined bysampling_rate, a record will be written and sent to the cloud.
Last updated
Was this helpful?