BYD ESS C648
Plugin
This plugin reads the BYD ESS C648 Containers
The Modbus Bus address cannot be anything other than
100
The Modbus configuration files for the C648 BYD battery have configurations based on specific RTUs (IP Addresses). You MUST find out the IP addresses of the
BMS
(2 x IP addresses), thePCS
(2 x IP addresses) and theADAS
(1 x IP address).The following data is collected at the stated intervals.
MAKE SURE that only the relevant configuration files are run against an RTU.
Source Map
To remain consistent with other installations of ESS, make sure you have a source map entry installed for ALL scenarios listed below
These are examples only. You need to replace the IP address to suit the installation site
For the
PCS
files
For the
BMS
files
For the
ADAS
files
BMS (RTU1 and RTU2):
These tasks must be run for PCS RTU1 and RTU2, which is a two different IP addresses
For each of RTU1 and RTU2, create the following scenarios:
PCS (RTU3 and RTU4):
These tasks must be run for PCS RTU3 and RTU4, which is a two different IP addresses
For each of RTU3 and RTU4, create the following scenarios:
ADAS (RTU5):
These 2 tasks must be run for ADAS RTU5, which is a single IP address
This data refers to the ADAS Container Modbus server. It is different from the PCS data.
For the ADAS RTU, create the following scenarios:
Last updated