Ingecon 100TL Inverters
Purpose
The purpose of this plugin is to collect data from Ingecon 100TL Inverters via Modbus.
Usage
This plugin reads the data from Ingecon 100TL Inverters via Modbus. This plugin relies on the Modbus Ardexa
plugin. It uses the Modbus TCP Specification, and collects from RS485 or TCP connected inverters. Inverter data will be collected to the solar
table. The plugin will be run every 5 minutes, by default. The following data is collected from the inverters. Strings data (DC Current
values below) will only appear if the String kit on
is connected
Arguments
Arguments are as follows:
endpoint
. This is either a serial device like/dev/ttyS0
or an IP or DNS like192.168.1.15
bus_addresses
. An RS485 address in the range 2-63. This can be a hyphenated list like3-10
or a list like2,5,7,9
--port
. This is an optional parameter used in an Ethernet gateway, and is the TCP port used for the gateway. Default is502
--attempts
. This is an optional parameter, and determines how many times to times to attempt to read an inverter value. Default is1
--delay
. This is the delay in seconds between inverter send and receive commands, AND ifattempts
> 1. Fractions like0.3
can be used. Default is0.05
Last updated