Huawei Logger

Purpose

Purpose of this plugin is to read from Huawei Solar Loggers using the Modbus protocol.

Usage

This plugin reads the Huawei Loggers and attached Inverters via Modbus. It uses the Modbus Specification and collects from IP connected inverters using TCP protocol. Inverter data will be collected to the solar table. There are a number of files that can be used to query the Huawei loggers depending on the version of the logger and the attached inverters. The huawei_sun2000.txt (default) file collects data for the Huawei 2000 logger. The other files are huawei_sun2000_60ktl huawei_sun2000_ktl.txt huawei_sl1000.txt huawei_sl3000.txt and huawei_logger_inverters.txt. Please ensure the file collects the data suitable for your logger.

The following Huawei SmartLogger models are supported:

SL1000 SL3000

The huawei_sun2000.txt config file is valid for the following inverter models:

SUN2000-50KTL-C1 SUN2000-50KTL SUN2000-42KTL SUN2000-36KTL SUN2000-33KTL-JP SUN2000-40KTL-JP SUN2000-43KTL-IN-C1 SUN2000-24.7KTL-JP SUN2000-40KTL-US SUN2000-33KTL-US SUN2000-36KTL-US SUN2000-33KTL-A SUN2000-8KTL -> SUN2000-28KTL

Other inverter models have their own dedicated configuration file.

For newer firmware versions of the same models, use the huawei_sun2000_v2.txt file as it has a Warning field and different scaling factors.

These should be read using the huawei_smart_logger.txt config file. The huawei_sl1000.txt and huawei_sl3000.txt config files are old and included for backwards compatibility. They are functionally identical and the same as the huawei_smart_logger.cmd.

Data will be run every 5 minutes by default. This plugin relies on the Modbus Ardexa plugin. The following data will be collected for the huawei_sun2000.txt file. For the other files contact Ardexa. Please also note that this plugin will ONLY collect data from TCP (not RS485 lines).

Run a log to send data to the cloud or a discover to only display information. You may need to configure the Huawei Logger for Modbus collection as follows:

1. Configure Settings->Modbus TCP
    a. If the Ardexa machine has a static address enable "Link Setting: Enable(Limited)" and 
    b. Add the IP address of the Ardexa device. If the Ardexa device is DHCP then make sure the "Link Setting: Enable(Unlimited)""
2. Address mode: Logical Address
3. SmartLogger address	(0-247): 1

Huawei Logger Data

The following logger data will be collected to the solar table for the huawei_smart_logger.txt file. This is the same list of data that is collected from the huawei_sl1000.txt and huawei_sl3000.txt config files.

Variable											Units
=========================================================
DC Power           									W  
AC Power           									W  
Cos Phi            									   
DC Current         									A  
Total Energy       									Wh 
Daily Energy       									Wh 
AC Current 1       									A  
AC Current 2       									A  
AC Current 3       									A  
Alarm 1            								   
Alarm 1 Raw            								   
Alarm 2            								   
Alarm 2 Raw          								   
Status             								   
Status Raw
Plant Status 1       								   
Plant Status 1 Raw       								   
Plant Status 2       								   
Plant Status 2 Raw   								   
Plant Status 3       								   
Plant Status 3 Raw  								   
Transfer Trip       								   
Transfer Trip Raw      								   
CO2 Reduction       								kg 
Reactive Power       								VAr
DC Current 2         								A  
Duration Of Daily Power Generation					h  
Active Alarm Sequence Number						   
Historic Alarm Sequence Number						   
Voltage 12  										V  
Voltage 23  										V  
Voltage 31  										V  
Inverter Efficiency    								%  
ESN      			 								   
Active Power Control Mode							   
Active Power Control Mode Raw				   
Reactive Power Control Mode						   
Reactive Power Control Mode	Raw					   
Reactive Power Scheduling Curve Mode   			   
Reactive Power Scheduling Curve Mode Raw  			   
Rated Plant Capacity   								W  
Total Rated Capacity Of Grid Connected Inverters	W  

Huawei SUN2000 Data

The following inverter data will be collected to the solar table for the huawei_sun2000.txt file. Other files collect different information. Please check each file for details.

Variable									Units
=================================================
Rated Power									W		
Output Mode										
Output Mode	Raw									
ESN												
DC Voltage 1								V		
DC Current 1								A		
DC Voltage 2								V		
DC Current 2								A		
DC Voltage 3								V		
DC Current 3								A		
DC Voltage 4								V		
DC Current 4								A		
DC Voltage 5								V		
DC Current 5								A		
DC Voltage 6								V		
DC Current 6								A		
DC Voltage 7								V		
DC Current 7								A		
DC Voltage 8								V		
DC Current 8								A		
AC Voltage 1								V		
AC Voltage 2								V		
AC Voltage 3								V		
AC Current 1								A		
AC Current 2								A		
AC Current 3								A		
Grid Freq									Hz		
Cos Phi									 		
Temperature									°C  	
Status 1									 		
Status 1 Raw									 		
Status 2									 		
Status 2 Raw									 		
Peak Daily Power							W		
AC Power									W		
Reactive Power								VA		
DC Power									W		
Daily Energy								Wh		
Total Energy								Wh		
Locking											
Locking Raw
Zero Voltage Ride-Through Protection On			
LVRT Protection On									
Islanding Protection On							
Insul Resist								Mohm	
DC Power 1									W		
DC Power 2									W		
DC Power 3									W		
DC Power 4									W		
Efficiency									%		
Reactive Power Compensation Mode					
Active Power Control Mode							
Active Power Derating Percentage			%		
Active Power Derating Value					W		
Active Power Deration Gradient				%/s	
Reactive Power Compensation Power Factor			
Reactive Power Compensation Q/S					
Reactive power adjustment time				s		
Alarm 1									 		
Alarm 2									 		
Alarm 3									 		
Alarm 4									 		
Alarm 5									 		
Alarm 6									 		
Alarm 7									 		
Alarm 8									 		
Alarm 9									 		
Alarm 10									 		
Alarm 1 Raw									 		
Alarm 2 Raw									 		
Alarm 3 Raw									 		
Alarm 4 Raw									 		
Alarm 5 Raw									 		
Alarm 6 Raw									 		
Alarm 7 Raw									 		
Alarm 8 Raw									 		
Alarm 9 Raw									 		
Alarm 10 Raw						 		

Huawei SUN2000-60KTL Data

The following inverter data will be collected to the solar table for the huawei_sun2000_60ktl.txt file. Other files will collect different information. Please check each file for details. Note: The DC Voltage values can go up to 10. The SL1000 units will not collect as much information as the Sun2000 model.

Variable           		Units
=============================
Rated Power             W
DC Voltage 1            V
DC Current 1            A
DC Voltage 2            V
DC Current 2            A
DC Voltage 3            V
DC Current 3            A
DC Voltage 4            V
DC Current 4            A
DC Voltage 5            V
DC Current 5            A
DC Voltage 6            V
DC Current 6            A
DC Voltage 7            V
DC Current 7            A
DC Voltage 8            V
DC Current 8            A
AC Voltage 1            V
AC Voltage 2            V
AC Voltage 3            V
AC Current 1            A
AC Current 2            A
AC Current 3            A
Grid Freq               Hz
Cos Phi
Cabinet Temperature     °C
Status
Peak Daily Power
AC Power                W
Reactive Power          VA
DC Power                W
Daily Energy            Wh
Total Energy            Wh
Insul Resist            Mohms
Alarm 1									 		
Alarm 2									 		
Alarm 3									 		
Alarm 4									 		
Alarm 5									 		
Alarm 6									 		
Alarm 7									 		
Alarm 8									 		
Alarm 9									 		
Alarm 10									 		
Alarm 1 Raw									 		
Alarm 2 Raw									 		
Alarm 3 Raw									 		
Alarm 4 Raw									 		
Alarm 5 Raw									 		
Alarm 6 Raw									 		
Alarm 7 Raw									 		
Alarm 8 Raw									 		
Alarm 9 Raw									 		
Alarm 10 Raw						 		
Warning
Warning Raw

Huawei SUN2000-KTL Data

The following inverter data will be collected to the solar table for the huawei_sun2000_ktl.txt file. Other files will collect different information. Please check each file for details. Note: The DC Voltage values can go up to 10. The SL1000 units will not collect as much information as the Sun2000 model.

Variable           		Units
=============================
Operating Status		   		
Operating Status Raw			
Connected						
Alarm1							
Alarm1 Raw						
Alarm2							
Alarm2 Raw						
Alarm3							
DC Voltage 1			V		
DC Current 1			A		
DC Voltage 2			V		
DC Current 2			A		
DC Voltage 3			V		
DC Current 3			A		
DC Voltage 4			V		
DC Current 4			A		
DC Voltage 5			V		
DC Current 5			A		
DC Voltage 6			V		
DC Current 6			A		
DC Voltage 7			V		
DC Current 7			A		
DC Voltage 8			V		
DC Current 8			A		
DC Voltage 9			V		
DC Current 9			A		
DC Voltage 10			V		
DC Current 10			A		
DC Voltage 11			V		
DC Current 11			A		
DC Voltage 12			V		
DC Current 12			A		
DC Voltage 13			V		
DC Current 13			A		
DC Voltage 14			V		
DC Current 14			A		
DC Voltage 15			V		
DC Current 15			A		
DC Voltage 16			V		
DC Current 16			A		
DC Voltage 17			V		
DC Current 17			A		
DC Voltage 18			V		
DC Current 18			A		
DC Power				W		
AC Voltage 1			V		
AC Voltage 2			V		
AC Voltage 3			V		
AC Current 1			A		
AC Current 2			A		
AC Current 3			A		
AC Power				W		
Reactive Power			var	
Cos Phi				    		
Grid Freq				Hz		
Efficiency				%		
Cabinet Temperature	°C		
Insul Resist			Mohms	
Status					 		
Status Raw				 		
Total Energy	        Wh		 
Daily Energy			Wh		 

Huawei SUN2000-8-28KTL Data

The following inverter data will be collected to the solar table for the huawei_sun2000_ktl.txt file. Other files will collect different information. Please check each file for details. Note: The DC Voltage values can go up to 10. The SL1000 units will not collect as much information as the Sun2000 model.

Variable           		Units
=============================
DC Voltage 1			V
DC Voltage 2			V
DC Voltage 3			V
DC Voltage 4			V
DC Voltage 5			V
DC Voltage 6			V
DC Current 1			A
DC Current 2			A
DC Current 3			A
DC Current 4			A
DC Current 5			A
DC Current 6			A
AC Power				W
AC Voltage 12			V
AC Voltage 23			V
AC Voltage 31			V
Cos Phi				    
Cabinet Temperature		°C
Reactive Power			VA
Grid Freq				Hz
Total Energy			Wh
Daily Energy			Wh
AC Current 1			A
AC Current 2			A
AC Current 3			A
Efficiency				%
DC Power MPPT 1			W
DC Power MPPT 2			W
DC Power MPPT 3			W
DC Power			    W
Status				        
Status Raw			        
Alarm 1					
Alarm 2					
Alarm 3					
Alarm 4					
Alarm 5					
Alarm 6					
Alarm 7					
Alarm 8					
Alarm 9					
Alarm 10					
Alarm 1 Raw				
Alarm 2 Raw				
Alarm 3 Raw				
Alarm 4 Raw				
Alarm 5 Raw				
Alarm 6 Raw				
Alarm 7 Raw				
Alarm 8 Raw				
Alarm 9 Raw				
Alarm 10 Raw								

Huawei SUN2000-100KTL Data

The following inverter data will be collected to the solar table for the huawei_sun2000_100ktl.txt file. Other files will collect different information. Please check each file for details. Note: The DC Voltage values can go up to 20.

Variable						Units
=====================================
Operating Status		    
Operating Status Raw		
Connected					
Alarm1						
Alarm1 Raw					
Alarm2						
Alarm2 Raw					
Alarm3						
Alarm3 Raw					
DC Voltage 1						V	
DC Current 1						A	
DC Voltage 2						V	
DC Current 2						A	
DC Voltage 3						V	
DC Current 3						A	
DC Voltage 4						V	
DC Current 4						A	
DC Voltage 5						V	
DC Current 5						A	
DC Voltage 6						V	
DC Current 6						A	
DC Voltage 7						V	
DC Current 7						A	
DC Voltage 8						V	
DC Current 8						A	
DC Voltage 9						V	
DC Current 9						A	
DC Voltage 10						V	
DC Current 10						A	
DC Voltage 11						V	
DC Current 11						A	
DC Voltage 12						V	
DC Current 12						A	
DC Voltage 13						V	
DC Current 13						A	
DC Voltage 14						V	
DC Current 14						A	
DC Voltage 15						V	
DC Current 15						A	
DC Voltage 16						V	
DC Current 16						A	
DC Voltage 17						V	
DC Current 17						A	
DC Voltage 18						V	
DC Current 18						A	
DC Voltage 19						V	
DC Current 19						A	
DC Voltage 20						V	
DC Current 20						A	
DC Power				    		W	
AC Voltage 1						V	
AC Voltage 2						V	
AC Voltage 3						V	
AC Current 1						A	
AC Current 2						A	
AC Current 3						A	
AC Power				    		W	
Reactive Power						var
Cos Phi				    			
Grid Freq							Hz	
Efficiency							%	
Cabinet Temperature					°C	
Insul Resist						Mohm
Status								 	
Status Raw							 	
Total Energy	            		Wh	
Daily Energy			    		Wh

Arguments

Arguments are as follows:

  • endpoint. This is either an IP address like 192.168.1.15

  • bus_addresses. The bus address of the inverter(s)

  • --port. This is an optional parameter used in an Ethernet gateway and is the TCP port used for the gateway. Default is 502

  • --attempts. This is an optional parameter and determines how many times to times to attempt to read an inverter value. Default is 1

  • --delay. This is the delay in seconds between inverter send and receive commands AND if attempts > 1. Fractions like 0.3 can be used. Default is 0.05

  • --timeout. This is the modbus command timeout in milliseconds. Default is 1000. This is only the timeout value in event of the modbus server not responding. If a modbus server responds sooner, then this value is ignored.

  • --socket_delay. Some Huawei equipment needs a delay between establishing a TCP socket and getting data. This feature allows this delay. It is defined in milliseconds.