Schneider ION Meters

Purpose

The purpose of this plugin is to collect data from Schneider ION Meters.

Usage

This plugin collects from the Schneider Electric ION , include the following models: ION7300 series, ION7500/7600, ION7550/7650, ION8600/8650 and ION8800. See: https://www.ccontrols.com/support/dp/ION_Meter_Modbus.pdf. It uses the Modbus TCP Specification, and collects from Serial or IP connected meters, though these meters are usually only conencted via TCP. Meter data will be collected to the meter table, and will be run every 5 minutes, by default. This plugin relies on the Modbus Ardexa plugin. The following data is collected:

Variable Name               Units
==================================
AC Power                    W
Apparent Power              VA
Reactive Power              var
AC Power 1                  W
AC Power 2                  W
AC Power 3                  W
AC Current 1                A
AC Current 2                A
AC Current 3                A
AC Voltage L1-N             V
AC Voltage L2-N             V
AC Voltage L3-N             V
AC Voltage L1-L2            V
AC Voltage L2-L3            V
AC Voltage L3-L1            V
Grid Freq                   Hz
Power Factor 1
Power Factor 2
Power Factor 3
Power Factor
Apparent Power 1	    VA
Apparent Power 2	    VA	
Apparent Power 3	    VA
Reactive Power 1	    VAR
Reactive Power 2	    VAR
Reactive Power 3	    VAR
Imported Energy             Wh
Exported Energy             Wh
Imported Reactive Energy    VARh
Exported Reactive Energy    VARh

Arguments

Arguments are as follows:

  • endpoint. This is either a serial device like /dev/ttyS0 or an IP or DNS like 192.168.1.15

  • bus_addresses. A Modbus address in the range 2-255. This can be a hyphenated list like 3-10 or a list like 2,5,7,9

  • --port. This is an optional parameter used in an Ethernet gateway, and is the TCP port used for the gateway. Default is 502

  • --attempts. This is an optional parameter, and determines how many times to times to attempt to read an inverter value. Default is 1

  • --delay. This is the delay in seconds between inverter send and receive commands, AND if attempts > 1. Fractions like 0.3 can be used. Default is 0.05

  • --stop_on_any_command_fail. If this is specified, then any Modbus commands that fail will stop all further queries for all bus addresses and attempts.

  • --serial_lock. If this is set, the program can only be run one at a time (so as not to overload a Modbus device). If the device being queried is a serial device, this will automatically be set to "on". For IP addresses it is optional.

  • --sampling_rate. If this is defined, and the sampling rate is greater than 1, then all values listed above will be collected as an average. In other words; it will take a sample at the nominated frequency. After X samples defined by sampling_rate, a record will be written and sent to the cloud.