Cube Meters

Purpose

The purpose of this plugin is to collect data from Cube Meters.

Usage

This plugin collects from the Metering Solutions Cube Meters, include the following models: Cube 350I (V2), Cube 350V (V2), Cube 400I (V2), Cube 400V (V2), Rail 350V. See: https://www.ndmeter.co.uk/cube-400.html. It uses the Modbus TCP Specification, and collects from Serial or IP connected meters, though these meters are usually only conencted via TCP. Meter data will be collected to the meter table, and will be run every 5 minutes, by default. This plugin relies on the Modbus Ardexa plugin. The following data is collected:

Variable Name               Units
AC Power                    W
Apparent Power              VA
Reactive Power              VAR
AC Power Demand             W
Apparent Power Demand       VA
Reactive Power Demand       VAR
AC Power 1                  W
AC Power 2                  W
AC Power 3                  W
AC Current 1                A
AC Current 2                A
AC Current 3                A
AC Current Average          A
AC Current N                A
AC Voltage L1-N             V
AC Voltage L2-N             V
AC Voltage L3-N             V
AC Voltage Average          V
AC Voltage L1-L2            V
AC Voltage L2-L3            V
AC Voltage L3-L1            V
Grid Freq                   Hz
Power Factor 1
Power Factor 2
Power Factor 3
Power Factor
AC Current 1 THD            %
AC Current 2 THD            %
AC Current 3 THD            %
AC Voltage L1-N THD         %
AC Voltage L2-N THD         %
AC Voltage L3-N THD         %
Imported Energy             Wh
Exported Energy             Wh

Arguments

Arguments are as follows:

  • endpoint. This is either a serial device like /dev/ttyS0 or an IP or DNS like 192.168.1.15

  • bus_addresses. A Modbus address in the range 2-255. This can be a hyphenated list like 3-10 or a list like 2,5,7,9

  • --port. This is an optional parameter used in an Ethernet gateway, and is the TCP port used for the gateway. Default is 502

  • --attempts. This is an optional parameter, and determines how many times to times to attempt to read an inverter value. Default is 1

  • --delay. This is the delay in seconds between inverter send and receive commands, AND if attempts > 1. Fractions like 0.3 can be used. Default is 0.05

  • --stop_on_any_command_fail. If this is specified, then any Modbus commands that fail will stop all further queries for all bus addresses and attempts.

  • --serial_lock. If this is set, the program can only be run one at a time (so as not to overload a Modbus device). If the device being queried is a serial device, this will automatically be set to "on". For IP addresses it is optional.

  • --sampling_rate. If this is defined, and the sampling rate is greater than 1, then all values listed above will be collected as an average. In other words; it will take a sample at the nominated frequency. After X samples defined by sampling_rate, a record will be written and sent to the cloud.